Measure Range and Input Impedance
|
|
Voltage
|
Current
|
Frequency
|
Phase
|
|
Range
|
30-450V
|
Direct: 10mA - 20A
|
45-65Hz
|
0-360°
|
|
Clamp: 200mA -100A
1A - 500A
4A - 2000A
|
Test Accuracy class, Resolution, and Basic Error
|
|
Accuracy Class
|
Resolution
|
Basic Error
|
|
Direct
|
Clamp
|
Direct
|
Clamp
|
|
Voltage (R.M.S)
|
0.1
|
0.2
|
0.01V
|
0.1%
|
0.2%
|
|
Current (R.M.S)
|
0.1
|
0.2
|
0.001A
|
0.1%
|
0.2%
|
|
Active Power
|
0.1
|
0.2
|
0.01W
|
0.1%
|
0.2%
|
|
Active Energy
|
0.1
|
0.2
|
┄
|
0.1%
|
0.2%
|
|
Reactive Power
|
0.2
|
0.5
|
0.01var
|
0.2%
|
0.5%
|
|
Reactive Energy
|
0.2
|
0.5
|
┄
|
0.1%
|
0.5%
|
|
Phase Angle
|
0.2
|
0.5
|
0.01°
|
0.2%
|
0.5%
|
|
Frequency
|
0.05
|
0.05
|
0.001Hz
|
0.02Hz
|
Operation and Storage Environment
|
|
Temperature (0C)
|
Humidity (%RH)
|
|
Operation Temperature
|
0 ~ 400C
|
15 ~ 90%
|
|
Storage temperature
|
-20 ~ 650C
|
10 ~ 90%
|
Weight and Dimensions
|
|
Meter
|
Aluminum carry case
|
|
Dimension
|
197×117× 45mm
|
450×300×140mm3
|
|
Net weight
|
0.4kg
|
4.0kg
|
Power Supply
|
|
AC Power
|
DC Power
|
|
Power Supply
|
100 ~ 240VAC
|
4.65 ~ 5.35VDC
|
|
Power Consumption
|
< 5VA
|
< 6W
|
|
Internal Batteries
|
Continue using time is about 4 hours.
|
|
|
|
|
| Application︰ | The SY3631 Energy Meter Testing Instrument is used to calibrate three phase, single phase, active or reactive energy meter under work, and also it can be used as voltage, current and power meter to measure AC parameter of three phase power line. |
| Functions and Features︰ | 1. Three phase active or reactive electricity energy meter; 2. Calibrate three phase, single phase, active or reactive meter; 3. Measure Vrms of three phase or single phase; 4. Measure Irms of three phase or single phase; 5. Measure active power of three phase or single phase; 6. Measure reactive power of three phase or single phase; 7. Measure apparent power of three phase or single phase; 8. Measure power factor of three phase or single phase 9. Measure phase angle between voltage and current; 10. Measure frequency of power line; 11. Display vector diagram; 12. Display waveform of U and I; 13. Analyze and display content of harmonic (up to 50 times) of U and I; 14. Store, look and transmit measured data (can storage 1000 testing data); 15. Inspect error of 48 kinds of wire connection ways of positive or adverse phase sequence on spot. 16. Connect to PC, reading record data and real-time measured data by PC, and download calibration parameter. |
| Payment Details︰ | TT, Paypal |
| Min Order︰ | 1 |
| Ship Date︰ | 30days after deposit |
|
|
| Select Image |
 |
|
|
|
|